Penetration sealing of disposal lines in mixed installation by fire protection sleeve / pipe sleeve
For cast lines with transitions to flammable pipes
Building services: Wastewater
For mixed installations acc. newsletter 02/2012 DIBt
Subsequent installation on standard Konfix connectors
At zero distance to further bulkheads (supply and ventilation bulkheads)
FOR PENETRATION SEALING OF PIPES MADE OF:
Cast iron, with diverging plastic pipes in accordance with DIBt specifications (DIBt newsletter 02/2012 ‘Metal pipes with connection to plastic pipes’)
Cast iron (main line) O ≤ 160 mm
Diverging pipes O ≤ 110 mm
Standard pipes: PVC, PP, PE-HD, LDPE, PB, PE-X, ABS, AS
Noise-insulating wastewater pipes:
Friatec Friaphon, Ostendorf Skolan, Geberit Silent dB 20 /PP, Rehau Raupiano Plus /Light, Wavin AS /SiTech, Poloplast Polo-Kal 3 S /XS /NG, Conel Drain, Pipelife Master 3 and many more
Recognized zero distance to third-party foreclosures (for details see paragraph 3.2)
SUPLY LINES
Fire-proof, insulated with mineral wool O ≤ 64 mm
Fire-proof, insulated with synthetic rubber O ≤ 64 mm (penetration sealing using CuraflamR Rollit ISOPro, for example)
Flammable, insulated with synthetic rubber O ≤ 63 mm (penetration sealing using CuraflamR XSPro or ECOPro)