ZZ® M20-S90

  • Stone penetration seal XS
  • Partitioning of cables, pipes and combinations
  • 90 minutes fire resistance
  • In lightweight partition walls, solid walls, gypsum walls, PRIOWALL type walls and solid ceilings
  • In angular component openings
  • Can be used as temporary or permanent fire insulation

Technical details

  • Lightweight partition walls, d ≥ 10 cm
  • Solid walls, d ≥ 10 cm
  • Gypsum wallboards, d ≥ 8 cm
  • PRIOWALL type walls, d ≥ 4.2 cm
  • Solid ceilings, d ≥ 15 cm
  • Bulkhead thickness, d ≥ 20 cm
  • Cables of all types (without internal cavities), ø ≤ 80 mm
  • Coaxial cable
  • Cable bundles, ø ≤ 100 mm, individual cables ø ≤ 21 mm
  • Fiber optic cables in bundled tubes ("speed pipe"), ø ≤ 100 mm
  • Plastic pipes, for liquids
  • Aluminum composite pipes, ø ≤ 63 mm
  • Steel, stainless steel, cast steel and copper pipes
  • Hydraulic pressure lines "AEROQUIP", ø ≤ 38.1 mm
  • Cable support structures made of steel, aluminum or
  • plastic may be routed through the penetration seal
  • EIectro installation pipes, flexible or rigid, made of plastic ø ≤ 63 mm, also as bundles ø ≤ 100 mm
  • Mineral wool mats or shells, including PVC sheathing if necessary
  • Flexible elastomer foam (FEF)
  • Foam glass pipe shells

Areas of use

  • Stone penetration seal XS
  • Partitioning of cables, pipes and combinations
  • 90 minutes fire resistance
  • In lightweight partition walls, solid walls, gypsum walls, PRIOWALL type walls and solid ceilings
  • In angular component openings
  • Can be used as temporary or permanent fire insulation

Product benefits

  • Simple and efficient installation, even for larger penetration seals
  • Very wide range of applications
  • Electrical installation conduits in large dimensions and bundles possible
  • Dust and fiber-free processing

  • ZZ 220-120 Fire protection brick, 200 x 120 x 60 mm
  • ZZ 300 Fire protection compound 310 ml cartridge
  • ZZ 333 Fire protection compound 310 ml cartridge
  • ZZ 330 Fire protection foam 380 ml cartridge, 2 x mixer attachment 2K
  • ZZ Label DE Combination label for systems according to abZ/abG

Please refer to the general type approval for detailed information on the areas of application and design regulations.

Media

skip
  • Installation situation

  • Installation situation

  • Installation situation

  • Installation situation

  • Installation situation