Penetration sealing of flammable and fire-proof insulated supply/ disposal lines
For flammable and fire-proof pipes
Building services: rainwater, drinking water, heating, cooling
• Variably adaptable to pipe and insulation dimensions • Extensive areas of application of the fire protection system • Zero distance possible in the system
APPLICATION AREAS
For penetration sealing of pipes made of:
Steel, stainless steel, cast iron ≤ 219.1 mm in ceiling*
Copper O ≤ 88.9 mm
PE-HD, PVC O ≤ 110 mm
Multi-layer composite O ≤ 110 mm
APPROVED FOR INSULATION 9–100 MM THICK:
Synthetic rubber
Rock wool (melting point > 1000°C)
Glass wool (melting point > 500°C)
Foam glass
*in ceiling O ≤ 326.0 mm)
Approved zero distance in system
In walls made of porous concrete, reinforced concrete, concrete, masonry and lightweight partitions with a thickness ≥ 150 mm
In lightweight partitions with a thickness ≥ 100 mm
In ceilings made of porous concrete, reinforced concrete, concrete with a thickness ≥ 150 mm
Two layers of CuraflamR Rollit ISOPro wrapped around both sides
Exception: single layer for mineral fibre insulation